No price development information for this product.
APC Smart-UPS VT Tower UPS 30kVA 400V with 3 Battery SYBT4 modules installed Expandable to 4. 24000 Watts / 30 kVA, Input 400V 3PH / Output 400V 3PH3PH. Runti
This product is end of life or currently not available.
Weight & dimensions | |
Weight | 536.8 kg |
Operational conditions | |
Operating relative humidity (H-H) | 0 - 95% |
Storage temperature (T-T) | -50 - 40 °C |
Operating temperature (T-T) | 0 - 40 °C |
Storage relative humidity (H-H) | 0 - 95% |
Battery | |
Battery recharge time | 5 h |
Typical backup time at half load | 18.3 min |
Typical backup time at full load | 5.5 min |
Hot-swap battery | ![]() |
Other features | |
Interface | DB-9, RS-232, Smart-Slot |
Dimensions (WxDxH) | 813 x 559 x 1499 mm |
Battery type | VRLA |
Nominal output voltage | 400 V |
Output voltage note | 380:400/415V 3 |
Output connections | - 3PH + G; - 3PH + N + G. |
Input connection type | 3PH + N + G |
Design | |
LED indicators | ![]() |
Product colour | Black |
Features | |
Audible alarm(s) | ![]() |
Emergency Power Off (EPO) | ![]() |
Output power capacity | 30 kVA |
Noise level | 55 dB |
Maximum current | 41 A |
Output power | 24000 W |
Logistics data | |
Products per pallet | 1 pc(s) |
EAN | 0731304257028 |
Warranty | 2 years |
Source: Icecat.biz |
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Scalable runtime
Allows additional run time to be quickly added as needed.
Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS overload condition or fault.
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
Battery replacement without tools
Allows quick, easy battery replacement.
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Shippable with modules installed
Enables pre-installation UPS staging and testing and faster installation.
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
Network manageable
Provides remote management of the UPS over the network.
InfraStruXure Manager Compatible
Enables centralized management via the APC InfraStruXure® Manager.
LCD display
Alpha-Numeric Display which displays system parameters and alarms.
Audible alarms
Provides notification of changing utility power and UPS conditions.
Programmable frequency
Ensures compatibility with different input frequencies.
LED status indicators
Quickly understand unit and power status with visual indicators.
SmartSlot
Customize UPS capabilities with management cards.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
Manual maintenance bypass
Reduces installation costs by eliminating the need for an external mechanical bypass.
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment. UL, FCC, CE, C-Tick approvals.
Cold-start capable
Provides temporary battery power when the utility power is out.
Estimated delivery: No delivery info
Today: 10:00 - 18:00
Estimated delivery: No delivery info
Today: 09:00 - 17:00
Estimated delivery: No delivery info
Today: 10:00 - 17:00
Estimated delivery: No delivery info
Today: 10:00 - 18:00
Estimated delivery: No delivery info
Today: 10:00 - 17:00